Intrinsic Safety – Auto-Switches & Pressure Switches for Hazardous Area Applications

 

  • ... According to clause 3.5.4 of AS/NZS60079.14:2009...

... If connected into an Intrinsic Safety circuit, a 'Simple Device' such as a 'contacts only' switch may be applied exempt from certification.

Simple Device = 'Contacts Only' Switch with no Energy Storage capacity (E.g.: without indicator lights, internal circuits or inductors for surge suppression, etc.).
Refer clause 5.7 of AS/NZS60079.11:2011 for defined examples of 'Simple Apparatus'.

2-wire Reed Switches as 'Simple Devices' (all spec'd without indicator light) & again wired into an Intrinsic Safety circuit:

      • D-C80, D-C80C
      • D-A90, D-A90V
      • D-A80, D-A80H, D-A80C
      • D-A67,
      • D-Z80,
      • D-E80A

Note: we cannot apply 'Contacts Protection Box' accessories (E.g.: CD-P11, CD-P12) as those would provide energy storage potential & nullify the 'Simple Apparatus' stature.

  • Pressure Switch: We could thus apply 'IS10-01S-6*' as a 'Simple Device' if wired into Intrinsic Safety circuit,